Speakers
Description
As part of the Advanced Photon Source Upgrade (APS-U), two high-power DC supplies for the L-Bend M1 and M2 magnets were installed. During the APS-U commissioning, a 1 Hz ripple was detected in the output currents of the M1/M2 and slow corrector supplies, leading to 1 Hz beam motion. This low-frequency harmonic originated from the booster ramping supply operating at 1 Hz, causing periodic grid voltage sags. This paper proposes an improved DC-Link voltage feedforward control for the M1/M2 supplies to reject grid disturbances, significantly attenuating the 1 Hz and other low-frequency ripples in the output currents. Combined with regulation circuit modification of the slow corrector power supplies, the 1 Hz harmonic was successfully eliminated from the beam motion.
Funding Agency
The work is supported by the U.S. Department of Energy, Office of Science, Office of Basic Energy Sciences, under Contract No. DE-AC02-06CH11357.
I have read and accept the Privacy Policy Statement | Yes |
---|---|
Please consider my poster for contributed oral presentation | Yes |
Would you like to submit this poster in student poster session on Sunday (August 10th) | No |