16–21 Aug 2026
Daejeon Convention Center
Asia/Seoul timezone

Implementation of an EPICS and EtherCAT-based PLC replacement system in PAL-XFEL

TUPO085
18 Aug 2026, 16:00
2h
1F Exhibition Hall (Daejeon Convention Center)

1F Exhibition Hall

Daejeon Convention Center

Poster Presentation MC4.A05: Other technology TUPO - Poster Session

Speaker

Geonyeong Mun (Pohang Accelerator Laboratory)

Description

PAL-XFEL is a fourth-generation X-ray free electron laser facility in Pohang, Korea. The existing operation mode PLC system interfaced with the Personnel Safety Interlock System (PSI) using a legacy embedded PLC platform that had reached end-of-life status. To replace the system while maintaining compatibility with the existing infrastructure, a new control system based on Raspberry Pi 5, EtherCAT I/O modules, and EPICS IOC was developed.

The EtherCAT master was implemented using EtherLab integrated directly into the EPICS IOC application. Existing dry-contact interfaces and EPICS PV naming structures were preserved using PV alias configuration, allowing the existing PSI ladder logic and operator interface to remain unchanged.

PREEMPT_RT Linux and CPU isolation techniques were applied to improve deterministic real-time performance. The developed system was successfully installed and verified through PSI interlock tests during PAL-XFEL maintenance operation.

I have read and accept the Privacy Policy Statement Yes

Author

Geonyeong Mun (Pohang Accelerator Laboratory)

Co-authors

Mr Gyujin Kim (Pohang Accelerator Laboratory) Soung Youl Baek (Pohang Accelerator Laboratory) YoungJin Suh (Pohang Accelerator Laboratory) DongCheol Shin (Pohang Accelerator Laboratory) Haeryong Yang (Pohang Accelerator Laboratory) Hoon Heo (Pohang Accelerator Laboratory)